Product features
Xdme series Ethernet PLC, including 60 point specification.
Compatible with all functions of XDM, with 2 Ethernet ports, supporting Ethernet communication
It is 12 times faster than XC series and has more internal resource space
Input type: NPN
Output type: Transistor (T)
Power specification: AC220V
Support x-net fieldbus function
Support high-speed counting (up to 80kHz), 10 axis pulse output (up to 100kHz), frequency measurement and other special functions
Two Ethernet ports, one 232 port and one 485 port are provided as standard
Support 1 ~ 16 expansion modules, 1 expansion ed and 2 expansion BD
Note: PNP PLC can be customized.
Basic specifications
project | Specifications |
Insulation voltage | DC 500V above 2m Ω |
Anti noise | Noise voltage 1000vp-p 1US pulse for 1 minute |
Air | No corrosive and combustible gas |
Ambient temperature | 0℃~60℃ |
Ambient humidity | 5%~95%(no condensation) |
USB port | nothing |
PORT1port | RS232, connecting the upper computer, man-machine interface programming or debugging |
PORT2port | RS485, connecting intelligent instrument, frequency converter, etc |
Ethernet port | RJ45 * 2, which connects the upper computer and monitoring, and communicates with other devices in the LAN |
Install | It can be fixed with M3 screws or directly installed on the guide rail |
Grounding (FG) | The third kind of grounding (not common grounding with strong current system) |
Performance specifications
Project | Specifications |
Program execution mode | Cyclic scanning mode |
Programming mode | Instruction and ladder diagram |
rocessing speed | 0.03us |
Outage hold | Use flashrom and lithium battery (3V button battery) |
User program capacity ※ 1 | 1MB
|
I/O point ※2 | Total points | 60points |
Input points | 36pointsX0~X43 |
Output points | 24pointsY0~Y27 |
Internal coil(X)※3 | 1280points:X0~X77、X10000~X11777、X20000~X20177、X30000~X30077 |
Internal coil(Y)※4 | 1280points:Y0~Y77、Y10000~Y11777、Y20000~Y20177、Y30000~Y30077 |
Internal coil (M、HM) | 87000 points | M0~M69999【HM0~HM11999】 |
Special use ※6 SM0~SM4999 |
technological process(S) | 9000 points | S0~S7999【HS0~HS999】 |
timer(T) | point | 7000 points | T0~T4999【HT0~HT1999】 |
Specifications | 100ms timer: setting time: 0.1 ~ 3276.7 seconds 10ms timer: setting time: 0.01 ~ 327.67 seconds 1ms timer: setting time: 0.001 ~ 32.767 seconds
|
Counter(C) | point | 7000points | C0~C4999【HC0~HC1999】 |
Specifications | 16 bit counter: setting value K0 ~ 32767 32-bit counter: set value - 2147483648 ~ + 2147483647
|
Data register(D) | 100000 words | D0~D69999【HD0~HD24999】 |
Special use ※ 6 sd0 ~ sd4999 |
FlashROM register (FD) | 14192 words | FD0~FD8191 |
Special use ※6 SFD0~SFD5999 |
High speed processing function | High speed counting, pulse output, external interrupt |
Password protection | ASCII length 6 bits |
Self diagnosis function | Power on self-test, monitoring timer, syntax check |
notes:
※ 1: user program capacity refers to the maximum program capacity during confidential download.
※ 2: I / O points refers to the number of terminals that users can access and output signals from the outside.
※ 3: X refers to the internal input relay, and X exceeding I points can be used as intermediate relay.
※ 4: y refers to the internal output relay. Y exceeding O points can be used as an intermediate relay.
※ 5: [] flag, which is the default power-off holding area and cannot be changed.
※ 6: special use refers to the special purpose register occupied by the system, which can not be used for other purposes. See Appendix 1 for details.
※ 7: the numbers of input coils and output relays / transistors are octal numbers, and the numbers of other memories are decimal numbers.
※ 8: I / O without real connection with peripheral equipment can be used as fast internal relay.
Function table configuration
× Not supported √ supported
signal communication
USB port | 232 port | signal communication | extend modular
| extend BD board
| Number of high-speed counting channels | Number of pulse output channels (T type / RT type) | External interrupt |
|
485 communication | Free communication | Incremental mode | AB phase |
|
XDME series |
XDME-60T10 | 0 | 1 | √ | √ | 16 | 2 | 10
| 10
| 10
| 10 |
Note: all models are equipped with clock function as standard.